Erickson Electrical Equipment Co. - Item # TMS467N
Erickson Electrical Equipment commercial metering equipment
Call Toll Free: 800-952-7225 - sales@ericksonelectric.com
home
about us
products
quote/info request
representation/contact us
Commercial Metering - 240V
Commercial Metering - 480V
Current Transformer Section with Disconnect
Current Transformer Cabinet
Accessories
THE CATALOG NUMBERS OF THE EQUIPMENT SHOWN IN THIS WEBSITE ARE NON UTILITY SPECIFIC. ANY EQUIPMENT INSTALLED IN A UTILITY SERVICE AREA MUST BE APPROVED BY THAT UTILITY AND CONFIGURED TO ITS REQUIREMENTS.

PLEASE CONTACT YOUR LOCAL REPRESENTATIVE OR OUR FACTORY REGARDING SPECIFIC UTILITY APPLICATIONS AND CATALOG NUMBERS. NOT ALL CATALOG NUMBERS ARE DISPLAYED IN THIS WEBSITE. IF YOU DO NOT SEE A CATALOG NUMBER YOU ARE LOOKING FOR, PLEASE CALL THE FACTORY DIRECT.
All Categories > Current Transformer Cabinet > Current Transformer Cabinet 400A - 2000A Wall Mounted > Main Circuit Breaker 400A - 1200A Top or Bottom Feed > Main Switch 400A - 1200A Top Feed > Item # TMS467N  
Request Information

Item # TMS467N




    Print Printable Page  
    Email Email This Page  
    Save To Favorites Save To Favorites
  


  • Switches accept 600 V class T fuses.
  • End covers are removable. Cover that is removed when connecting termination box to meter panel is to be installed on end meter panel unit.
  • Enclosures are type 3R, for outdoor or indoor use.


480Y/277V Fusible Main Switch

larger image

Dimensional Drawing

larger image



Specifications · Features · Application

Specifications

Current Rating

800 A

Dim. A

38 1/2 in

Dim. B

64 in

Dim. C

13 7/8 in

Lugs (No. Wires/Lug & Size)

(2) 600 MCM
(4) 250 MCM-#1/0

Enclosure

Type 3R Aluminum

Voltage

277 V
480 V

Connection Type

Wye

Short Circuit Rating @ 480V

200,000 RMS Sym. Amps.

Use

Indoor
Outdoor

Approvals

Approvals
UL Listed



Features
  • Type 3R enclosures for outdoor, or indoor installations.
  • Short circuit current ratings of 200,000 rms symmetrical amperes @ 480 V, but not more than withstand ratings of branch overcurrent devices.
  • Copper bus bar, silver plated or tin plated
  • Aluminum enclosures install easily, never rust.
  • Main lugs are suitable for copper or aluminum conductors.
  • Listed by underwriters laboratories INC, As switches, miscellaneous, File E-52975.




Application
    For use with Erickson type '6CM' commercial metering panel boards where main fusible switches are indicated or desired.